How can we help you today?
What is the maximum fuse ratings for 25kV and 38kV HVL/cc switchgear?
Issue:
Maximum fuse ratings for 25kV and 38kV HVL/cc switchgear
Product Line:
HVLcc.
Environment:
Products sold in the United States.
Cause:
Application.
Resolution:
The maximum fuse ratings for 25kV and 38kV HVL/cc switchgear are:
25kV - 180A (2 - 100E fuses in parallel)
38kV - 117A (2 - 65E fuses in parallel)
CTA-ID : 2011448
Maximum fuse ratings for 25kV and 38kV HVL/cc switchgear
Product Line:
HVLcc.
Environment:
Products sold in the United States.
Cause:
Application.
Resolution:
The maximum fuse ratings for 25kV and 38kV HVL/cc switchgear are:
25kV - 180A (2 - 100E fuses in parallel)
38kV - 117A (2 - 65E fuses in parallel)
CTA-ID : 2011448