What is the duty cycle for the ATS48 unit?
Issue:
ATS48 duty cycle
Resolution:
In standard duty applications, the ATS48 soft starter supports reliable motor starting under moderate stress conditions. It provides:
- 400% of rated current (In) for up to 12 seconds, or
- 300% of rated current (In) for up to 23 seconds
These ratings are based on a 50% load factor and allow up to 10 starts per hour, or an equivalent level of thermal cycling.
Severe Duty Applications
For more demanding applications, the ATS48 soft starter is designed to handle higher thermal stress. It provides:
- From a cold state:
- 400% of rated current (In) for up to 48 seconds, or
- 300% of rated current (In) for up to 90 seconds
- Under cyclic operation:
- 400% of rated current (In) for up to 25 seconds, with a 50% load factor and up to 5 starts per hour, or an equivalent thermal cycling
In severe duty operation, the motor thermal protection complies with Class 20 thermal overload protection, ensuring enhanced protection for the motor under heavy-duty conditions.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.