What should be considered when using 125°C cable in metal enclosed switchgear?
Issue:
Considerations when using a 125°C cable in metal enclosed switchgear.
Product Line:
Switchgear
Environment:
Installation / Setup
Resolution:
Per ANSI C37.20.3-1987 Table 3, connection to insulated cables: The limit of Hottest-Spot Temperature Rise is 45°C and Total Temperature Temperature is 85°C. Per paragraph 4.5.5 - This temperature limitation is based on the use of 90°C insulated power cables.
The switch has been tested and rated based on 90°C cable connections only. If the customer is using 125°C cable, the ampacity rating for the cable must be based on the 90°C rating for the conductor size.
Considerations when using a 125°C cable in metal enclosed switchgear.
Product Line:
Switchgear
Environment:
Installation / Setup
Resolution:
Per ANSI C37.20.3-1987 Table 3, connection to insulated cables: The limit of Hottest-Spot Temperature Rise is 45°C and Total Temperature Temperature is 85°C. Per paragraph 4.5.5 - This temperature limitation is based on the use of 90°C insulated power cables.
The switch has been tested and rated based on 90°C cable connections only. If the customer is using 125°C cable, the ampacity rating for the cable must be based on the 90°C rating for the conductor size.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.