How can we help you today?
What stress cones do we recommend for HVL/cc Switchgear?
Issue:
What stress cones do we recommend for HVL/cc Switchgear?
Product Line:
HVLcc
Environment:
Products sold in the United States.
Cause:
Assembly/Installation
Resolution:
HVL/cc terminations
Cables Standard Termination Height
24`` from floor to fuse support lug landing
24``from top plate to switch terminals
Top pullbox can increase distance to 40``
Stress cone (installed length)
RAYCHEM
5kV - 10.5``
15kV - 15``
25kV - 28``
35kV - 33``
3M COLD SHRINK
Stress cone (installed length)
5kV - 28kV -- 16.5``
34.5kV - 20.5``
What stress cones do we recommend for HVL/cc Switchgear?
Product Line:
HVLcc
Environment:
Products sold in the United States.
Cause:
Assembly/Installation
Resolution:
HVL/cc terminations
Cables Standard Termination Height
24`` from floor to fuse support lug landing
24``from top plate to switch terminals
Top pullbox can increase distance to 40``
Stress cone (installed length)
RAYCHEM
5kV - 10.5``
15kV - 15``
25kV - 28``
35kV - 33``
3M COLD SHRINK
Stress cone (installed length)
5kV - 28kV -- 16.5``
34.5kV - 20.5``
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.