How can we help you today?
Can there be top entry or top exit on N3R HVL/cc switchgear.
No, there cannot be TOP entry or top exit on N3R HVL/cc switchgear.
The options to resolve this are rear entry/exit with the use of optional rear extensions.
Also, Side entry or exit can be done with the addition of an incoming/outgoing terminal chamber.
The roof design of the N3R HVL/cc is not compatible with entering conduits. In addition, the conduits would enter directly over the switch terminals. The HVL/cc has reduced clearances and should not have any moisture dropping down on top of the switch.
CTA-ID : 2011855
The options to resolve this are rear entry/exit with the use of optional rear extensions.
Also, Side entry or exit can be done with the addition of an incoming/outgoing terminal chamber.
The roof design of the N3R HVL/cc is not compatible with entering conduits. In addition, the conduits would enter directly over the switch terminals. The HVL/cc has reduced clearances and should not have any moisture dropping down on top of the switch.
CTA-ID : 2011855
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.