How Do You Configure an ATS48 Soft Starter for Heavy-Duty Applications?
Resolution:
The ATS48 soft starter does not include a specific setting or switch labeled “Heavy Duty.”
To handle heavy-duty applications, follow these configuration best practices:
-
Oversize the Soft Starter
Select a soft starter one size larger than the motor rating, based on the motor’s full load current (FLA). -
Adjust the Overload Class
In addition to the default programming, set the motor thermal protection to a higher class:- Navigate to: PRO → THP (thermal protection parameter)
- Set the overload class to Class 20
- Oversizing ensures the soft starter can handle higher starting currents and longer acceleration times typical of heavy-duty loads.
- Setting Class 20 provides extended thermal protection suitable for demanding applications such as conveyors, crushers, or high-inertia loads.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.