Do the U-Line starters have integrated suppression? What type of suppressor do we use?
Issue:
Identify if the U line has an integrated suppressor module.
Product Line:
TeSys U IEC Starters
Environment:
IEC Contactors and Starters
Resolution:
U-Line starters have integrated suppression. The LUC's A1 & A2 terminals are connected to a high power carbon resistor (used as current/voltage damper) connected in series with a varistor limiting electronic circuit control voltage available at its terminals. Capacitors (to cope with circuit current demand) are connected in parallel with the varistor. The coil itself has a diode + Zener diode to limit the voltage on de-energization to around 24v. No additional suppression is required.
Identify if the U line has an integrated suppressor module.
Product Line:
TeSys U IEC Starters
Environment:
IEC Contactors and Starters
Resolution:
U-Line starters have integrated suppression. The LUC's A1 & A2 terminals are connected to a high power carbon resistor (used as current/voltage damper) connected in series with a varistor limiting electronic circuit control voltage available at its terminals. Capacitors (to cope with circuit current demand) are connected in parallel with the varistor. The coil itself has a diode + Zener diode to limit the voltage on de-energization to around 24v. No additional suppression is required.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.