What are the properties of the 15kV insulators used in Metal Enclosed Switchgear?
Issue:
Properties of the 15kV insulators used in Metal Enclosed Switchgear
Product Line:
Metal Enclosed Switchgear
Environment:
Product Features
Resolution:
15KV INSULATOR PROPERTIES
POLY EPOXY PORCELAIN
IMPULSE WITHSTAND 95 KV 95 KV 95 KV
60 HZ WITHSTAND 1MIN DRY 36 KV 36 KV 36 KV
LEAKAGE DISTANCE 6.0 IN 12.4 IN 6.87 IN
STRIKE DISTANCE 6.0 IN 6.0 IN 6.0 IN
CANTILEVER STRENGTH 1250 LB 1250 LB 1250 LB
TENSILE STRENGTH 3000 LB 3000 LB 3000 LB
COMPRESSION STRENGTH 20,000 LB 20,000 LB20,000 LB
TRACK RESISTANCE 1500 MIN N/A NO TRACK
BREAKAGE/CHIPPING LOW LOW HIGH
NEMA GPO-3 INSULATION
MATERIAL GLASS POLYESTER LAMINATE
UL94 FLAME CLASS 94V-0
TEMPERATURE INDEX 130C
HIGHLY FLAME RETARDANT ELECTRICAL / 160 C MECHANICAL CLASS B
AND LOW SMOKE GENERATING
Properties of the 15kV insulators used in Metal Enclosed Switchgear
Product Line:
Metal Enclosed Switchgear
Environment:
Product Features
Resolution:
15KV INSULATOR PROPERTIES
POLY EPOXY PORCELAIN
IMPULSE WITHSTAND 95 KV 95 KV 95 KV
60 HZ WITHSTAND 1MIN DRY 36 KV 36 KV 36 KV
LEAKAGE DISTANCE 6.0 IN 12.4 IN 6.87 IN
STRIKE DISTANCE 6.0 IN 6.0 IN 6.0 IN
CANTILEVER STRENGTH 1250 LB 1250 LB 1250 LB
TENSILE STRENGTH 3000 LB 3000 LB 3000 LB
COMPRESSION STRENGTH 20,000 LB 20,000 LB20,000 LB
TRACK RESISTANCE 1500 MIN N/A NO TRACK
BREAKAGE/CHIPPING LOW LOW HIGH
NEMA GPO-3 INSULATION
MATERIAL GLASS POLYESTER LAMINATE
UL94 FLAME CLASS 94V-0
TEMPERATURE INDEX 130C
HIGHLY FLAME RETARDANT ELECTRICAL / 160 C MECHANICAL CLASS B
AND LOW SMOKE GENERATING
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.