What is the AIC rating of our Type S lighting contactors?
Issue:
Would like to know the AIC rating of our Type S lighting contactors
Product Line:
NEMA and Definite Purpose Contractors and Starters
Environment:
North American Products
Resolution:
A lighting contactor does not actually have an AIC rating as it is not a circuit interrupter. It does have withstand ratings and this information can only be found on the sticky-back label that comes with the contactors. Here`s the data:
Type S 30 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 40 A current limiting circuit breaker, Cat. No. IFL34040; 100k @ 600V when protected by 30 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V; 10k @ 480V or 5k @ 600V when protected by a 40 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 60 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 90 A current limiting circuit breaker, Cat. No. IFL34090; 100k @ 600V when protected by 60 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V. And 18k @ 480V or 14k @ 600V when protected by an 80 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 100 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 125 A current limiting circuit breaker, Cat. No. IKL34125; 100k @ 600V when protected by 100 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V; 10k @ 600V when protected by a 125 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 200 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 225 A current limiting circuit breaker, Cat. No. IKL34225; 100k @ 480V when protected by 200 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 480V; 14k @ 600V when protected by a 250 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 300 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 400 A current limiting circuit breaker, Cat. No. ILL34400; 100k @ 600V when protected by 400 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V; 22k @ 600V when protected by a 400 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Would like to know the AIC rating of our Type S lighting contactors
Product Line:
NEMA and Definite Purpose Contractors and Starters
Environment:
North American Products
Resolution:
A lighting contactor does not actually have an AIC rating as it is not a circuit interrupter. It does have withstand ratings and this information can only be found on the sticky-back label that comes with the contactors. Here`s the data:
Type S 30 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 40 A current limiting circuit breaker, Cat. No. IFL34040; 100k @ 600V when protected by 30 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V; 10k @ 480V or 5k @ 600V when protected by a 40 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 60 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 90 A current limiting circuit breaker, Cat. No. IFL34090; 100k @ 600V when protected by 60 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V. And 18k @ 480V or 14k @ 600V when protected by an 80 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 100 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 125 A current limiting circuit breaker, Cat. No. IKL34125; 100k @ 600V when protected by 100 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V; 10k @ 600V when protected by a 125 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 200 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 225 A current limiting circuit breaker, Cat. No. IKL34225; 100k @ 480V when protected by 200 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 480V; 14k @ 600V when protected by a 250 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Type S 300 A - Suitable for use on a circuit capable of delivering not more than 100k @ 480V when protected by a 400 A current limiting circuit breaker, Cat. No. ILL34400; 100k @ 600V when protected by 400 A max. UL Listed Class RK5 branch circuit current limiting fuses having interrupting rating not less than 100k @ 600V; 22k @ 600V when protected by a 400 A max. UL Listed thermal magnetic (inverse-time) circuit breaker.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.