Can a PowerPact P and R frame breaker with a standard Micrologic trip unit be upgraded to a type A, P, or H trip unit?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
ModelProtectionCat. #
2.0 (IEC only)LSOS132R
3.0 (UL/ANSI only) LIS131A
5.0LSIS133A
2.0A (IEC only)LSOS142R
3.0A (UL/ANSI only) LIS141A
5.0ALSIS143A
6.0ALSIGS144A
5.0PLSIS163A
6.0PLSIGS164A
5.0HLSIS173A
6.0HLSIGS174A


Pic of trip unit replacement
For R frame and for P frame (excluding motorized, rotary handle, and drawout), they also need the following parts:
Connector S33100
External Voltage Sensing kit S64203 (P and H trip units only, if voltage sensing is required)
BCM S64205 (if modbus is required)

For P frame drawout, they need the following parts:
Connector S33101
External Voltage Sensing kit S64209 (P and H trip units only, if voltage sensing is required)
BCM S64206 (if modbus is required)

For P frame motorized, they need the following parts:
Connector S33100
External Voltage Sensing kit S64210 (P and H trip units only, if voltage sensing is required)
BCM S64207 (if modbus is required)

For P frame with rotary handle, they need the following parts:
Connector S33100
External Voltage Sensing kit S64210 (P and H trip units only, if voltage sensing is required)
BCM S64205 (if modbus is required)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.