How can we help you today?

Customer asks what is used for a space heater element in the H.V. switchgear?

Issue:
What product is used for the space heater element in the medium voltage switchgear?

Product Line:
Switchgear.

Environment:
Products sold in the United States.

Cause:
Product features

Resolution:
The heaters vary from product to product. HVL, HVL/cc, Visi/Vac, Metalclad. They may also vary by available control voltage and with or without guards.

The standard heater at this time for Metalclad for 120V applications with guards is the Heatrex 565074. This is a 500W 240V heater which is run at 120V. The Square D part number is 46028-126-01. There are 4 heaters per vertical section.


Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.