Issue:
Handle electrical interlock for 8539SCG44 with GJL breaker disconnect.
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
Type S Combination Starters
Cause:
Repair parts for combination starters
Resolution:
There are NO external auxiliary interlock kits available for the operating mechanism used to operate the Type GJL circuit breaker. One auxiliary contact (NO or NC) can be added to the inside of circuit breaker case. This contact module can be added at any time. Operating mechanism must be removed in order to install the contact module.
Note:
Be aware that the status of the contacts will change when when the circuit breaker trips in addition to the breaker being turned ON and OFF.
Contact Module information:
1. Catalog number is AAC
2. Form ``C`` contact arrangement
CTA-ID : 2014543
Released for: Schneider Electric USA