Why don't the AL800P6K and AL800P6K4 lugs fit on the ON side of the PowerPacT P frame, unit mount breaker?
Issue:
Lug kits for P-frame breaker will not install on to the line side of the breaker.

Product line:
Molded case circuit breakers

Resolution:
The arc chute cover gets in the way. These lugs can only be mounted on the OFF end for P frame, as noted on instruction sheet 48049-135-03.