Will the PQ3610G plug-in unit install correctly onto a 3P4W busway?
Issue:
PQ3610G plug-in unit installation onto a 3P4W busway
Product Line:
Busway
Environment:
Installation / Setup
Resolution:
Yes. However, there will not be a connection to the neutral bar in the busway. This is true for any plug-in unit up to and including the 600 Amp plug. Above the 600A rating you CANNOT install a 3P plug onto a 4P busway.
PQ3610G plug-in unit installation onto a 3P4W busway
Product Line:
Busway
Environment:
Installation / Setup
Resolution:
Yes. However, there will not be a connection to the neutral bar in the busway. This is true for any plug-in unit up to and including the 600 Amp plug. Above the 600A rating you CANNOT install a 3P plug onto a 4P busway.
Released for: Schneider Electric USA