How can we help you today?

Can a 3-pole breaker be used in a 2-pole application?

Article available in these languages:

  • Spanish

Issue:
Three pole breaker use in two pole (single-phase) application

Product Line:
MCCB

Environment:
Powerpact and Masterpact

Resolution:
  • A 3p breaker can be used on a 3 phase system using either 2 or 3 poles.
  • A 3p breaker can be used on a 1 phase system only if indicated by the markings as noted below.
For reference:
  • Per NEC article 240.85: "A circuit breaker with a straight voltage rating, such as 240V or 480V, shall be permitted to be applied in a circuit in which the nominal voltage between any two conductors does not exceed the circuit breaker’s voltage rating."
  • According to UL's White book, "3–pole circuit breakers are suitable for use on 3-phase systems only, unless marked to indicate use on 1-phase systems, such as, “For 1–phase connections, use two outside poles,” or an equivalent statement. A 3-pole breaker used in place of a 2-pole breaker on a 3-phase system, such as a 2-pole breaker used in a branch circuit that is actually two legs of a 3-phase system, is acceptable without the 3-pole breaker being specifically marked."

Powerpact M P and R
  • Three-pole M, P, and R frame breakers have a marking on the cover that states "single phase any 2 poles."
Powerpact L
  • Three-pole Powerpact L frame Micrologic breakers with all trip units (U31X, U33X, U43X, U44X, U53X and U54X) are marked for single-phase use, but on 240Vac circuits only.  Use any 2 poles.
Powerpact H and J
  • Three-pole Powerpact H and J-frame thermal-magnetic breakers are marked for single phase use, including MCP.
  • Three-pole Powerpact H and J-frame Micrologic breakers with standard trip units (U31X and U33X) are marked for single-phase use
Powerpact B
  • Three-pole Powerpact B frame breakers are not marked for single phase use.
Powerpact Q
  • Three-pole Powerpact QB, QD, QG, QJ breakers are not marked for single phase use.
EDB EGB EJB
    • Three-pole EDB, EGB, and EJB breakers are not marked for single phase use.
      LA LH LAL LHL
      • Three-pole LA and LH type breakers are marked for single phase use.  Use any two poles.
      Legacy Breakers
      • Some three-pole legacy breakers are marked for single-phase use but most are not.  Check the label for marking.

      Schneider Electric USA

      Users group

      Discuss this topic with experts

      Visit our community and get advice from experts and peers on this topic and more
      • Help Center
      • Contact Sales
      • Find our Offices
      • Where to Buy
      • Tech Support: 877-342-5173
      • Careers
      • Company Profile
      • Investors
      • Newsroom
      • Report a Misconduct
      • Product Documentation
      • Software and Firmware
      • Product Selector
      • Product Replacement
      • DigestPLUS Online Catalog
      • Industries
      • Partners
      • Schneider Electric Community
      • Events
      • Privacy Policy
      • Cookie Notice
      • Terms of use
      • Change your cookie settings