How can the display be set to show a specific parameter as the default the Altistart 48?

Article available in these languages:

Issue:
Set display to show specific parameters as the default the ATS48.

Resolution:
The factory setting displays the motor current (parameter LCr).
To save the chosen display:
You must make these changes from the keypad on the face of the starter itself.  These changes can not be made via the remote keypad, if present.
- Press the ENT key once: the choice is temporary, it will be cleared at the next power up.
- Press the ENT key again for 2 seconds: the display flashes, the choice is permanent and will be retained even if power is cycled.

The available display parameters are:
COS - power factor
LCr - Line current
rnt - hours of run time
LPr - Line power in terms of percentage nominal
Ltr - motor torque in terms of percentage nominal
LAP - Power in terms of kW
EtA - Soft Starter status (rdy, acc, dec, run etc.)
LFt - Last fault detected
PHF - Phase rotation
COd - keypad locking code

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.