Do the LK3 switches have horsepower ratings?
Issue:
Checking if the LK3 switches are horsepower rated.
Product Line:
LK3 Disconnect Switches
Environment:
Operating Mechanisms and Disconnect Switches
Resolution:
Yes. They are as follows:
Switch Voltage Max. HP Rating/Max. Motor FLC
LK3 30A 240V 7.5/22
480V 15/21
600V 20/22
125Vdc 3/25 (w/2poles in series)
250Vdc 5/20 (w/2poles in series)
LK3 60A 240V 15/42
480V 30/40
600V 50/52
125Vdc 3/25 (w/2poles in series)
250Vdc 10/38 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 100A 240V 30/80
480V 60/77
600V 75/77
125Vdc 7.5/58 (w/2poles in series)
250Vdc 20/72 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 200A 240V 60/154
480V 125/156
600V 150/144
125Vdc 15/112 (w/2poles in series)
250Vdc 40/140 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 400A 240V 125/312
480V 250/302
600V 350/336
125Vdc 20/148 (w/2poles in series)
250Vdc 50/173 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 600A 240V 200/480
480V 400/477
600V 350/336
125Vdc 20/148 (w/2poles in series)
250Vdc 50/173 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 800A, 1000A, 1200A 240V 250/602
480V 500/590
600V 500/472
Checking if the LK3 switches are horsepower rated.
Product Line:
LK3 Disconnect Switches
Environment:
Operating Mechanisms and Disconnect Switches
Resolution:
Yes. They are as follows:
Switch Voltage Max. HP Rating/Max. Motor FLC
LK3 30A 240V 7.5/22
480V 15/21
600V 20/22
125Vdc 3/25 (w/2poles in series)
250Vdc 5/20 (w/2poles in series)
LK3 60A 240V 15/42
480V 30/40
600V 50/52
125Vdc 3/25 (w/2poles in series)
250Vdc 10/38 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 100A 240V 30/80
480V 60/77
600V 75/77
125Vdc 7.5/58 (w/2poles in series)
250Vdc 20/72 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 200A 240V 60/154
480V 125/156
600V 150/144
125Vdc 15/112 (w/2poles in series)
250Vdc 40/140 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 400A 240V 125/312
480V 250/302
600V 350/336
125Vdc 20/148 (w/2poles in series)
250Vdc 50/173 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 600A 240V 200/480
480V 400/477
600V 350/336
125Vdc 20/148 (w/2poles in series)
250Vdc 50/173 (w/3poles in series in one of the following conditions: 3 poles on +, 2 poles on + and 1 on -, 1 pole on + and 2 on -, 3 poles on -).
LK3 800A, 1000A, 1200A 240V 250/602
480V 500/590
600V 500/472
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.