What are the replacement lugs for the LA, LH, and Q4 type circuit breakers?
Product Line:
LA LH Q4 circuit breakers
Resolution:
The standard replacement lugs are catalog number AL400LA, which contains 1 lug per kit.
Several alternate lug kits are available, listed below:
Mechanical Lug Kit
"T" indicates control wire taps on the lugs.
See instruction bulletin, 48040-896-03
Compression Lugs
See instruction bulletin, 48040-699-03
Power Distribution Connectors
See instruction bulletin, 48040-929-04
LA LH Q4 circuit breakers
Resolution:
The standard replacement lugs are catalog number AL400LA, which contains 1 lug per kit.
Several alternate lug kits are available, listed below:
Mechanical Lug Kit
| Lug Kit | Conductor |
| AL400LA AL400LAT | (1) 1 AWG-600 kcmil AI/Cu (42-304 mm2) (2) 1 AWG-250 kcmil AI/Cu (42-127 mm2) |
| CU400LA | (1) 1 AWG-600 kcmil Cu (42-304 mm2) (2) 1 AWG-250 kcmil Cu (42-127 mm2) |
| AL400LH7 AL400LH7T | (1) 1 350-750 kcmil AI/Cu (177-380 mm2) |
| AL250LAMC | (1) 250-350 kcmil Al (42-304 mm2) (1) 3/0 AWG-350 kcmil Cu (85-177 mm2) |
"T" indicates control wire taps on the lugs.
See instruction bulletin, 48040-896-03
Compression Lugs
| Lug Kit | Conductor |
| VC400LA3 | (2) #4 AWG-300 kcmil AI/Cu (25-150 mm2) |
| VC400LA35 | (2) 250-350 kcmil AI/Cu (120-185 mm2) |
| VC400LA5 | (1) #2/0 AWG-500 kcmil AI/Cu (70-240 mm2) |
| VC400LA7 | (1) 500-750 kcmil AI (240-400 mm2) (1) 500 kcmil Cu (240 mm2) |
| CVC400LA3 | (2) #2/0 AWG-300 kcmil AI/Cu (70-150 mm2) |
| CVC400LA5 | (1) 250-500 kcmil AI/Cu (120-240 mm2) |
See instruction bulletin, 48040-699-03
Power Distribution Connectors
| Lug Kit | Conductor |
| PDC4LA250 | (3) 14-2 AWG Cu, (1) 2 AWG-250 kcmil Cu |
| PDC6LA20 | (6)12-2/0 AWG Cu |
| PDC12LA4 | (12) 14-4 AWG Cu |
See instruction bulletin, 48040-929-04
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.