What is the power terminal lug data for the LC1D80 and LP1D80 contactor?

Issue:
What is the clamp terminal wire size of LC1D80 and LP1D80 contactor?

Product Line:
IEC Contactors and Starters

Environment:
IEC TeSys D Contactor Accessories

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One #10-2 AWG or Two #10-4 AWG per terminal.
stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
solid cable: One #10-3 AWG or Two #10-2 AWG per terminal.