What is the inrush and sealed VA rating of an 8910DPA 75A and 90A contactor coil?
Issue:
Power consumption on an 8910DPA 75A and 90A contactor coil?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Class 8910 Types DP, DPA Contactors

Resolution:
The coil burden is 214VA inrush and 19VA sealed.