Can a QO2150, QO2175, QO2200, QO2150VH, QO2175VH, QO2200VH, or QOB2150VH breaker be installed in a 3 phase load center?
Issue:
Is it possible to install a 2p, 150 - 200 A QO or QO-VH or 2p, 150 A QOB-VH breaker on a 3 phase panelboard or load center?
Product Line:
QO Circuit Breakers
Resolution:
No. The QO2150, QO2150, QO2200, QO2150VH, QO2150VH, QO2200VH, or QOB2150VH branch circuit breakers are two pole breakers that are physically four poles wide and connect to four adjacent connector fingers in the load center or panelboard. They connect to four connector fingers to adequately carry the higher ampacity. If these branch breakers would be installed in a 3 phase load center, a phase to phase short circuit would be created.
Is it possible to install a 2p, 150 - 200 A QO or QO-VH or 2p, 150 A QOB-VH breaker on a 3 phase panelboard or load center?
Product Line:
QO Circuit Breakers
Resolution:
No. The QO2150, QO2150, QO2200, QO2150VH, QO2150VH, QO2200VH, or QOB2150VH branch circuit breakers are two pole breakers that are physically four poles wide and connect to four adjacent connector fingers in the load center or panelboard. They connect to four connector fingers to adequately carry the higher ampacity. If these branch breakers would be installed in a 3 phase load center, a phase to phase short circuit would be created.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.