How do I configure an ATS48 soft starter to test a small motor?

Article available in these languages:

Resolution:

To configure the ATS48 soft starter for testing a motor with significantly lower power than the starter’s rating, follow these steps:

  1. Go to the DRC (Drive Configuration) menu.
  2. Set the SSt (Small Motor Test) parameter to On.

What this does:

  • Activating SSt allows the soft starter to safely operate a small motor during testing or maintenance.
  • It automatically disables the CLP (Torque Control) function, which is not needed for small motor testing.

Important notes:

  • Default state:
    • OFF = Function disabled
    • On = Function enabled
  • The SSt parameter resets to OFF when control voltage is removed.
  • After power is restored:
    • The PHF fault setting and CLP parameter revert to their original configuration.

This feature is particularly useful when testing high-power soft starters with low-power motors.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.