On Energy Efficient Transformers ending in T151HCT, why is there an H0 terminal? How is it wired?
Issue:
H0 Terminals on T151HCT Transformers
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
T151HCT Transformers have 480V Wye primaries
Resolution:
To properly wire the primary of an EE***T151HCT Transformer, the H0 terminal, if there is one, is not to be connected. Connect only the H1, H2, and H3 terminals to the 480V primary source.
H0 Terminals on T151HCT Transformers
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
T151HCT Transformers have 480V Wye primaries
Resolution:
To properly wire the primary of an EE***T151HCT Transformer, the H0 terminal, if there is one, is not to be connected. Connect only the H1, H2, and H3 terminals to the 480V primary source.