What are the contact ratings for the 8501C relays with DC rated contacts?
Issue:
How are the 8501C relays rated for DC across the contacts?
Product Line:
Relays and Timers
Environment:
8501 Square D Power Relays
Resolution:
For SPDT versions 20 amps at 110 volts DC and 8 amps at 220 volts DC.
For DPDT versions 10 amps at 110 volts DC and 4 amps at 220 volts DC.
The devices utilize blow out magnetic coils to handle these DC loads.