What Are The Contact Ratings of 9998SO1 and 9999SO4 Control Circuit Contact Blocks?

Issue:
Need to know what maximum current the internal overload relay contact can handle.

Product Line:
Contactors and Starters

Environment:
NEMA Type S Starters

Resolution:
The contacts are rated NEMA B600 which is as follows:

5.00 Amp Maximum Continuous Carrying Current.
Maximum Make Volt-Amp 3600, Maximum Break Volt-Amp 360.
Voltage Make (amps)Break (amps)
12030 A3 A
24015 A1.5 A
4807.5 A0.75 A
6006 A0.6 A