How can we help you today?

What Causes an StF Fault on an ATS48 Soft Starter and How Can It Be Resolved?

Resolution:

The StF fault on an ATS48 soft starter indicates that the starting time is too long (excessive starting time).

This typically means the motor did not reach full speed within the configured time limit.

Possible Causes and Solutions:

  • Mechanical issues:
    Inspect the driven equipment for wear, excessive friction, poor lubrication, misalignment, or blockages.

  • Incorrect starting time setting (tLs):
    Verify the tLs parameter in the PrO menu and adjust it if necessary to allow sufficient acceleration time.

  • Improper sizing:
    Ensure the soft starter and motor are correctly sized for the application’s load requirements.

Addressing these areas should help clear the fault and allow normal startup operation.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.