How can the program settings and parameters be transferred from one drive to another with an Altivar 58 drive?

Issue:
Transfering parameters from an ATV58 to another ATV58.

Resolution:
Save Parameters from the Source Drive

  1. Ensure the drive is not receiving a Run command.
  2. Verify that the keypad is unlocked.
  3. Navigate to Menu 7 – Files Menu.
  4. Select Operation Type (FOt) and press ENT.
  5. Select Store File (Str) and press ENT.
  6. Choose a file location (1–4) and press ENT.
  7. The display will flash while the parameters are being saved. When the process is complete, the display returns to FOt.

Load Parameters to the Target Drive

  1. Remove the keypad and connect it to the destination ATV58 drive.
  2. Confirm that the destination drive has the same horsepower (HP) rating and firmware revision as the source drive.
  3. Make sure the drive is not receiving a Run command.
  4. Go to Menu 7 – Files Menu.
  5. Select Operation Type (FOt) and press ENT.
  6. Select Recall File (rEC) and press ENT.
  7. Choose the same file location (1–4) used when saving the parameters and press ENT.
  8. When “Wiring OK?” appears, verify that loading the parameters will not create an unsafe or unexpected drive operation. If safe, press ENT.
  9. When “Validate ENT/ESC” appears, press ENT to confirm that you want to overwrite the existing parameters.
  10. After the transfer is complete, the display returns to FOt, indicating that the parameters have been successfully copied.

Note: For additional information and detailed instructions, refer to the ATV58 keypad programming guide.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)





Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.