How can we help you today?

Does the XUB5ANANL2 photoelectric sensor have any LED indicators?

Yes, one yellow LED to indicate an output.


CTA-ID : 2020703

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.