What is the difference between a K4 and a K13 rated Transformer?
Issue:
Difference between a K4 and a K13 rated Transformer.
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
Variations of K Ratings for Transformers
Resolution:
The K4 Transformer is used in applications in which a major portion of the load is non-linear devices, and the 24 hour average load duty cycle is 80% or higher. The K13 rated Transformer is used where the majority of the load is non-linear, and the 24 hour average load duty cycle is 95% or higher. In practical applications, ratings higher than K13 are never necessary.
Difference between a K4 and a K13 rated Transformer.
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
Variations of K Ratings for Transformers
Resolution:
The K4 Transformer is used in applications in which a major portion of the load is non-linear devices, and the 24 hour average load duty cycle is 80% or higher. The K13 rated Transformer is used where the majority of the load is non-linear, and the 24 hour average load duty cycle is 95% or higher. In practical applications, ratings higher than K13 are never necessary.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.