The PBQ3640G is listed for both 240 and 600 volt applications. How does it accommodate both fuse sizes?

Issue:
Fuse base adjustments in the PBQ3640G

Product Line:
I-Line Busway Fusible plug in units

Environment:
Products sold and used in North America

Resolution:
The PBQ3640G is shipped with 600 volt fuse spacing.
The installation instructions provided explain how to relocate the load side fuse bases for use with 240 volt fuses.