How do the Micrologic trip units respond to harmonic loads?
Product Line:
Circuit Breaker Micrologic Trip Units

Resolution:
The Micrologic Trip Unit samples the current waveform to provide true RMS sensing and protection through the 15th harmonic.

Harmonic trip units measure FFT (fast fourier transform) of odd harmonics up to 31st harmonic (percentage of RMS value with respect to RMS value of the fundamental).

Beyond this, the trip units cannot accurately monitor current, so protection is not guaranteed and nuisance tripping is likely.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings