Can a Three Phase Isolation Transformer with the Standard Delta Primary be Applied on a Wye Configuration Power System?

Issue:
Transformer Power is Often Provided by a Wye Service.
Product Line:
LV Transformers
Environment:
Applies to Three Phase SquareD/Schneider Electric Transformers
Cause:
Most Three Phase Transformers by SquareD/Schneider Electric have Delta Primaries
Resolution:

Yes, a three-phase, Delta primary isolation Transformer can be used on any three-phase system.  Similar to a motor, the Transformer Delta Primary only needs to have the correct three-phase voltage applied to its terminals, with no Neutral connection necessary.