Do the Class 9065 Type SP Motor Logic Plus Overload Relays provide ground fault detection?
Issue:
Do solid State overload relays provide ground fault detection?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment
9065 Solid state overload relays
Resolution:
Yes, this solid state overload relay calculates ground fault condition based on a summation of the three phase current. It is adjustable from 0.15 times minimum over current setting to 0.20 times the maximum over current setting. Please note that the device is for equipment protection and in no way should be used as people protection. Additionally, this solid state overload is not intended to take the place of branch circuit protective devices, such as circuit breakers or fuses.
Do solid State overload relays provide ground fault detection?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment
9065 Solid state overload relays
Resolution:
Yes, this solid state overload relay calculates ground fault condition based on a summation of the three phase current. It is adjustable from 0.15 times minimum over current setting to 0.20 times the maximum over current setting. Please note that the device is for equipment protection and in no way should be used as people protection. Additionally, this solid state overload is not intended to take the place of branch circuit protective devices, such as circuit breakers or fuses.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.