What is a current limiting circuit breaker?

Issue:
What is a current limiting circuit breaker?

Product Line:
Molded Case Breaker, Powerpact

Resolution:
A current limiting circuit breaker is one that has been certified by UL to limit the let-through I^2t (I squared t) during a fault to not more than the I^2t available during a half cycle of the prospective symmetrical short circuit current. Maximum let-through I^2t and peak current levels are published on curves available with the trip curves for the current limiting breakers.