{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Are the concentric knockouts in the load centers, metering, or safety switches rated for grounding (or bonding) in accordance with the NEC, using a standard nipple or connector?

Article available in these languages: Spanish

Issue:
Product Design Features

Product Line:
Load Centers, Safety Switches and Metering

Resolution:
No. There is no test in the UL standards for these product lines for the knockouts of the enclosures. The test for this requirement is found in UL 514A (Standard for Safety - Metallic Outlet Boxes) only. The enclosures for load centers, metering, and safety switches are manufactured to the UL 50 standard. The installer MUST use a "Bonding Bushing" for such a connection or follow what the code requires.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: