What are the permissible mounting orientations for NEMA motor starters?

Issue:
Mounting orientations for NEMA motor starters

Product Line:
Nema and Definite Purpose and Starters

Environment:
Contactors and Starters

Cause:
Needs the permissible mounting orientations for NEMA motor starters.

Resolution:
All devices must mount in the vertical plane. For NEMA sizes 00 - 4, the device may be mounted so that it is rotated 90 degrees clockwise or counterclockwise. For NEMA sizes 5 and above, the device must remain in the vertical position.