Can power poles be added to the Class 8903 Type SQ 100 amp lighting contactor?
Issue:
Adding a power pole to 8903SQ 100 AMP Lighting Contactor
Product Line:
Contactors and Starters
Environment:
Lighting Contactors
Resolution:
Power poles may be added in the field or in the factory for any Class 8903 Type S lighting contactor. However power pole adders are only available in 30 or 60 amp modules which can be normally open or normally closed. See page 14-125 for filed addition selection or page 14-112 for factory modification of Digest 173. Note maximum number of power poles is 5.
Adding a power pole to 8903SQ 100 AMP Lighting Contactor
Product Line:
Contactors and Starters
Environment:
Lighting Contactors
Resolution:
Power poles may be added in the field or in the factory for any Class 8903 Type S lighting contactor. However power pole adders are only available in 30 or 60 amp modules which can be normally open or normally closed. See page 14-125 for filed addition selection or page 14-112 for factory modification of Digest 173. Note maximum number of power poles is 5.
Released for: Schneider Electric USA