How can we help you today?

Do we offer replacement coils for the CA2K, CA3K, CA4K relays?

Issue:
Does TeSys™ K IEC Style Control Relays line has replacement coils?

Product Line:
Relays and Timers

Environment:
Tesys CAK

Resolution:
K-Line relay coils are not replaceable.

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.