Is it possible to use one variable speed drive to run multiple motors at one time?


Resolution:

Yes. A single Variable Speed Drive (VSD) can operate multiple motors simultaneously, provided that all motors are intended to run at the same speed and frequency. Since the drive supplies a common output frequency, independent speed control of individual motors is not possible.

Conditions

The following conditions must be met when using one drive to control multiple motors:

  • All motors must start and run at the same time.
  • All motors will operate at the same output frequency commanded by the drive.
  • The combined motor load must not exceed the drive's rated capacity.
  • The application must not require individual motor speed regulation.
  • Each motor will need to have its own motor thermal protection device.

Drive Sizing and Configuration

When selecting and programming the drive:

  • Set the Nominal Motor Current parameter to the sum of the Full Load Amps (FLA) of all connected motors.
  • Set the Rated Motor Power parameter to the total horsepower (HP) or kilowatt (kW) rating of all connected motors.
  • Verify that the sum of all motor currents does not exceed the drive's rated output current.
  • Verify that the total motor power does not exceed the drive's rated power.

Protection Requirements

The drive's internal motor overload protection is designed for a single motor and does not adequately protect multiple motors connected in parallel.

Therefore:

  • Each motor must have its own overload and/or over-temperature protection device.
  • Individual motor protection must comply  with Article 430, Part C of the National Electrical Code, and any applicable local electrical
    codes.
  • An overload event on one motor must either:
    • Command the drive to stop, or
    • Disconnect the affected motor from the drive output

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)




Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.