Can Masterpact or Powerpact circuit breakers with Micrologic trip units be used on 400 Hz electrical systems?
Product Line:
Masterpact and Powerpact Circuit breakers
Environment:
Products used in the US
Resolution:
Masterpact breakers and Powerpact M, P, and R frame breakers cannot be used on 400Hz systems.
Powerpact H, J, and L-frame breakers can be used on 400Hz systems, but need to be derated. See the catalog
for H, J, and L-frame derating information. (Note: Not UL Listed)
0611CT1001
Masterpact and Powerpact Circuit breakers
Environment:
Products used in the US
Resolution:
Masterpact breakers and Powerpact M, P, and R frame breakers cannot be used on 400Hz systems.
Powerpact H, J, and L-frame breakers can be used on 400Hz systems, but need to be derated. See the catalog
for H, J, and L-frame derating information. (Note: Not UL Listed)
0611CT1001
Released for: Schneider Electric USA