Which wire should be removed from Class 8536 Type S starter to configure for separate source control?
Issue:
What wire should be removed from Class 8536 Type S starter to configure for separate source control?
Product Line:
Nema and Definite Purpose Contactors and Starters
Environment:
North American Products
Cause:
Needs the know Which wire should be removed from Class 8536 Type S starter to configure for separate source control.
Resolution:
Remove jumper wire between terminal L2 of contactor and ``COM`` terminal (for melting alloy overload) or Terminal 96 (for solid state overload) on overload relay contact module. This applies to size 00 through size 5 only. For conversion of size 6 or 7 consult Marketing Product Support Group.
Released for: Schneider Electric USA