Issue:
What size of control wire should be used to connect a shunt trip for the H, J and L frame breaker?
Product Line:
Powerpact H, J and L frame
Resolution:
Each terminal may be connected by one 18–14 AWG (1.0–2.5 mm²) stranded copper wire. Terminals used should be C1 and C2.