What is the wire range for the Powerpact R frame breaker with an RLTB kit?

Product Line:
Circuit Breakers

Resolution:
The RLTB is a terminal pad kit where lugs are mounted, so the wire range depends on the lugs used.
The lug kit we offer for mounting on the RLTB is AL2500RK, which includes two lugs per kit, and each will accept (1) 1/0 to 750 kcmil. A total of 8 lugs can be installed per terminal.