How can we help you today?
Why does the FFTK screen occasionally display "Failed" when performing the short time test right after the long time test in automatic mode for Micrologic A, P, and H trip units?
Issue:
"Failed" indication during Automatic Trip Curve Test with Full Function Test Kit (FFTK)
Product Line:
FFTK for Micrologic A/P/H trip units
Resolution:
This is normal due to the overlapping short time and long time curves. Wait at least 10 seconds after the long time test before performing the short time test.
"Failed" indication during Automatic Trip Curve Test with Full Function Test Kit (FFTK)
Product Line:
FFTK for Micrologic A/P/H trip units
Resolution:
This is normal due to the overlapping short time and long time curves. Wait at least 10 seconds after the long time test before performing the short time test.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.