How can we help you today?

What is the Short Circuit Current Rating (SCCR) for ANY of the PAK, ServicePak Power Outlet Panels?

Issue:
Design product features

Product Line:
Power Outlet Panels - PAK

Resolution:
The Short Circuit Current Rating(SCCR) for ANY of the PAK, Power Outlet Panels is 10,000 rms symmetrical amperes at 120/240Vac maximum. The SCCR CANNOT be increased.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.