Can the EDB, EGB, and EJB type breakers be used on 400 Hz systems?
Product Line:
Circuit Breakers
Resolution:
Yes. The thermal derating for all amperages is 0.97. The magnetic rerating multiplier is 2.6. The interrupting rating is 10% of the 60 Hz interrupting rating.
NOTE: NOT UL LISTED
Circuit Breakers
Resolution:
Yes. The thermal derating for all amperages is 0.97. The magnetic rerating multiplier is 2.6. The interrupting rating is 10% of the 60 Hz interrupting rating.
NOTE: NOT UL LISTED
Released for: Schneider Electric USA