Issue:
Ground fault alarm only is required, not ground fault trip.
Product Line:
Molded Case Circuit Breakers
Resolution:
No, the Micrologic 6.0P and 6.0H trip units cannot be used for ground fault alarm only. These trip units have both ground fault alarm AND trip.
If a breaker is required with ground fault alarm only, then use the Micrologic 5.0P or 5.0H trip unit.
Ground fault alarm only is required, not ground fault trip.