What is the 800 ampere main breaker used in an I-Line panel interior, catalog number HCP36868M? Can this be changed to a 600A breaker?
Issue:
Replacement main breaker
Product Line:
Panelboards
Environment:
I-Line
Cause:
Maintenance, Conversion
Resolution:
The factory-installed main breaker in the HCP36868M is MGP36800. Customer can install an MGP36600 breaker to make the panel 600 amperes.
Replacement main breaker
Product Line:
Panelboards
Environment:
I-Line
Cause:
Maintenance, Conversion
Resolution:
The factory-installed main breaker in the HCP36868M is MGP36800. Customer can install an MGP36600 breaker to make the panel 600 amperes.
Released for: Schneider Electric USA