Is there a way to test ground fault on a Masterpact NW or NT breaker and not trip the breaker?

Issue:
Ground fault test in Masterpact breaker
Product Line:
Air Circuit Breaker
Resolution:
NO. Primary injection tests, the use of the full function test kit, and the ground fault test button on the front of the trip unit will all trip the breaker.