Can a 5.0 or 5.0A trip unit be used for ground fault alarm without tripping?

Issue:
How to set up and test ground fault alarm in Micrologic trip units

Product Line:
Molded Case and Air Circuit Breaker

Resolution:
No. Neither the 5.0 nor 5.0A trip units can be used because those trip units do not have the required programming functionality.
To get ground fault alarm without tripping, replace the trip unit with a 5.0P or 5.0H trip unit, add an M2C or IO programmable contact module, and program the trip unit for the alarm.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings